    Hi:
    How do I wiring a heat pump to cool only with 2 low volts cable from the air handler



    Last edited by Pricer Air; Today at 04:52 AM.


    Reason: mispelling






  • Quote Originally Posted by Pricer Air
    View Post

    Hi:

    How do I wiring a heat pump to cool only with 2 low volts cable from the air handler

    You’d listed as a contractor?







  • What Brand is the Outdoor Unit ?

    Most manufacturers energize the “Reversing Valve” on Cooling mode (Rheem & Ruud , maybe Ameristar , energize in “Heat”) If the unit has an “O” terminal on the Board it means the Rev Valve energizes in Cooling , so it must get power when AC is needed , and if the unit has “B” means the Rev Valve energizes in Heating which means it wont need power at all, because its already in Cooling mode

    (Although sometimes B can be “common” on older units, so follow your wires to see where they go)

    So if your unit energizes in cooling “O” …. you just wire “O” to come on with “Y”

    We cannot give you any more information about wiring … that is all you get

    Tell your Cat I said “Psst Psst Psst”






  • Quote Originally Posted by pecmsg
    View Post

    You’d listed as a contractor?

    Dude … I know 2 contractors who are TERRIBLE when it comes to wiring

    Granted both are Foreigners

    1 called me last week “how do I bypass the door switch”

    Tell your Cat I said “Psst Psst Psst”






  • Quote Originally Posted by Snapperhead
    View Post
    Dude … I know 2 contractors who are TERRIBLE when it comes to wiring

    Granted both are Foreigners

    Maybe is resi comfort cooling adopted common wire colors it would be better.

    Did some amistar units (supplied by building owner) and they used purple wire for the w signal. Like really. Purple….
    And they used black wire to the common term where I see most people use blue.

    Sent from my iPhone using Tapatalk